Home β€Ί Manufacturers β€Ί Siemens β€Ί LGK16.335A27
Siemens

Siemens LGK16.335A27 230V Gas, Oil, Dual-Fuel Burner Control

Siemens LGK16.335A27 230V Gas, Oil, Dual-Fuel Burner Control.

● In Stock 12-Mo Warranty Same-Day Dispatch Ships Worldwide πŸŽ– Veteran-Owned
In Stock β€” Ready to Ship
ManufacturerSiemens
Part numberLGK16.335A27
Supply Voltage 240V (230V) AC
Pre-purge time 37s
Pre-ignition time 5s
Safety time 2.5s
Get a price for LGK16.335A27
Response within 1 business hour

All orders subject to availability

πŸ›‘
12-month warranty
All units tested
⚑
Same-day dispatch
Order by 2pm CST
🌐
Worldwide delivery
US, EU, Asia, Middle East
πŸŽ–
Veteran-owned
CAGE: 9NK75
Controls gas, oil, or dual-fuel burners Suitable for continuous and intermittent operation Self-checking flame supervision Integrated air pressure supervision CE certified

The Siemens LGK16.335A27 is engineered for the precise control of gas, oil, or dual-fuel forced draft burners. Operating at 240V (230V), this control unit features a prepurge time of 37s, a pre-ignition time of 5s, and an ignition safety time of 2.5s. Its design ensures safe and reliable operation for continuous and intermittent burner cycles.

This burner control is ideal for industrial and commercial applications, including those requiring mandatory self-checking flame supervision. It offers air pressure supervision for precise air damper control, making it suitable for multi-stage or modulating burner systems. Tested to EN298 and CE certified, it meets stringent safety and electromagnetic compatibility standards.

Stanlo Automation, a veteran-owned surplus parts distributor, is your trusted source for the Siemens LGK16.335A27. We specialize in providing quality surplus industrial automation components to keep your operations running efficiently.

Supply Voltage240V (230V) AC
Pre-purge time37s
Pre-ignition time5s
Safety time2.5s
Post purge time15s
Permissible afterburn time15s
Power Consumption3.5 VA
Gas-fired combustion plants
Oil-fired combustion plants
Dual-fuel burners
Industrial heating systems
Boiler sequencing
Multi-stage burners
Modulating burners
QRA5 UV detector Ionization electrode
Siemens LGK 16.335A27 Siemens 230V Burner Control Siemens Combustion Control
This unit serves as a reliable replacement or compatible alternative for other Siemens LGK16 series burner controls.
Expert tip
This control requires a separate plug-in base, which should be ordered separately.
1
Email confirmation
Immediate receipt acknowledgment sent to you
2
Account manager assigned
Confirms your part's spec and condition
3
Your quote delivered
Tailored to your specific requirements
What are the main technical specifications for the Siemens LGK16.335A27?
The Siemens LGK16.335A27 operates on a 230V supply, featuring a 37s prepurge time, 5s pre-ignition time, and a 2.5s safety time. It has a power consumption of 3.5 VA and is designed for gas, oil, and dual-fuel burners.